AKF10 LON

Duct/Immersion sensor for measuring air temperature and other gaseous media for HVAC applications (e.g. supply and exhaust ducts) with pocket Ø=6 mm for faster response. Can be used as an immersion temperature sensor combined with a thermowell pocket.

Measuring values temperature
Network technology LON FT (free topology)
Power supply 15..24 V = (±10%) or 24 V ~ (±10%) SELV
Power consumption typ. 0,5 W (24 V =) | 1,7 VA (24 V ~)
Operating temperature range permissible working temperature, pocket -45..+130 °C, enclosure: -35..+70 °C
Accuracy temperature ±0,5 K (typ. at 21 °C)
Enclosure PA6, pure white, with quick lock screws
Protection IP65 according to EN 60529
Cable entry M20 for wire max. Ø=8 mm, seal insert for double cable entry for wire max Ø=6 mm
Connection electrical terminal block, max. 1,5 mm²
Pocket stainless steel V4A, Ø=6 mm, mounting length: 50 | 100 | 150 | 200 | 250 | 300 | 450 mm
Ambient condition max. 85% rH short term condensation
Weight 160 g
Mounting for duct sensors please use mounting flange MF6DS flexible or MF6 (brass), for immersion sensors please use immersion pocket THVADS / THMSDS
Delivery contents incl. mounting flange
Contact

Contact us:


Thermokon Sensortechnik GmbH
Platanenweg 1
35756 Mittenaar
Tel.: +49 2778 6960-0


Write email


View contact