OF14 passive
Surface-mounted sensor for temperature measurement on glass or similar surfaces. Designed for connecting to controls and display systems.
Measured values | temperature |
---|---|
Output passive | PT100 | PT100 1/3 DIN | PT1000 | PT1000 1/3 DIN | Ni1000 | Ni1000TK5000, NTC10k | NTC 10k Precon | NTC5k | NTC20k | NTC1,8k, LM235Z |
Measuring range temp. | -35..+70 °C |
Operating temperature range | permissible working temperature, -35..+70 °C |
Accuracy temperature | depending on used sensor, PT100 | PT1000: ±0,3 K (typ. at 0 °C, Kl.B), Ni1000: ±0,4 K (typ. at 0 °C), Ni1000TK5000: ±0,4 K (typ. at 0 °C), NTC10K: ±0,22 K (typ. at 25 °C), depending on length of connection wire |
Sensor | 2-wire (standard), 3-wire or 4-wire |
Protection (IP) | IP65 according to EN 60529, SI-Protection (not possible for electronic Sensors) |
aluminium, dimensions: 35x10x6 mm | |
Ambient condition | -35..+70 °C, max. 85% rH short term condensation |
Weight | 45 g |
Mounting | surface mounting due to self-adhesive sensor surface |
Notes | other sensors and cable lengths on request |