OF14+ active

Sensor for temperature measurement on glass surfaces or similar in enclosure USE-S. Designed for control and monitoring applications.

Measuring valuestemperature
Output voltageTRV: 1x 0..10 V, min. load 5 kΩ
Output ampereTRA: 1x 4..20 mA, max. load 500 Ω
Power supplyTRV: 15..24 V = (±10%) or 24 V ~ (±10%) SELV, TRA: 15..24 V = (±10%) SELV
Power consumptionTRV: typ. 0,4 W (24 V =) | 0,8 VA (24 V ~), TRA: typ. 0,5 W (24 V =)
Output signal range temp.Scaling analog output, 0..+50 °C (default setting), selectable from 8 temperature ranges -50..+50 | -20..+80 | -15..+35 | -10..+120 | 0..+50 | 0..+100 | 0..+160 | 0..+250 °C, adjustable at the transducer
Operating temperature rangepermissible working temperature, pocket 0..+50 °C, enclosure: -35..+70 °C
Accuracy temperature±0,5 K (typ. at 21 °C)
Enclosureenclosure USE-S, PC, pure white
ProtectionIP65 according to EN 60529
Cable entryFlextherm M20 for wire Ø=4,5..9 mm, removable
Connection electricalremovable plug-in terminal, max. 2,5 mm², connection wire PVC, 2x Ø=0,25 mm², grey, 1 m (default), 2 m, 4 m, 6 m, for other lengths please request
Pocketaluminium, dimensions: 35x10x6 mm
Ambient conditionmax. 85% rH short term condensation
Weight115 g
Mountingsurface mounting due to self-adhesive sensor surface
Delivery contentsincl. mounting base enclosure USE-S pure white
Notesother cable lengths on request
Contact

Contact us:


Thermokon Sensortechnik GmbH
Platanenweg 1
35756 Mittenaar
Tel.: +49 2778 6960-0


Write email


View contact