AF25 passive

Contact sensor with connection cable and brass strap used to measure the surface temperature of pipes (cold or hot water) and other contact surfaces. Tightening strap/tension clamp and thermal contact fluid are available as accessories.

Measuring values temperature
Output passive PT100 | PT100 1/3 DIN | PT1000 | PT1000 1/3 DIN | Ni1000 | Ni1000TK5000, NTC10k | NTC 10k Precon | NTC5k | NTC20k | NTC1,8k
Measuring range temp. -35..+100 °C, optionally: -50..+135 °C (T135)
Operating temperature range permissible working temperature, -35..+100 °C, optionally: -50..+135 °C (T135)
Accuracy temperature depending on used sensor, PT100 | PT1000: ±0,3 K (typ. at 0 °C, Kl.B), Ni1000: ±0,4 K (typ. at 0 °C), Ni1000TK5000: ±0,4 K (typ. at 0 °C), NTC10K: ±0,22 K (typ. at 25 °C), depending on length of connection wire
Sensor 2-wire (standard), 3-wire or 4-wire
Protection IP65 according to EN 60529, SI-Protection
Pocket brass, mounting length 35 mm, Ø=7 mm
Ambient condition max. 85% rH short term condensation
Weight 45 g
Notes other sensors and cable lengths on request