NOVOS 7
The NOVOS 7 stands out for its well-known and intuitive user interface using a rotary push button and a 3.5" TFT display. Four favourite buttons allow quick access to frequently used functions such as temperature set point or light control. Blinds and lights can thus be configured accordingly. The NOVOS 7 can be equipped with up to 4 integrated sensors (temperature, relative humidity, CO2 and VOC) and contributes to a comfortable room ambience and energy savings.
Measured values | temperature, humidity, CO2, VOC (depending on the device) |
---|---|
Network technology | RS485 Modbus |
Power supply | 24 V = (±10%) or 24 V ~ (±10%) SELV |
Power consumption | typ. 2 W (24 V =) |
Measuring range temp. | -50..+50 °C | 0..+50 °C | -20..+80 °C | -15..+35 °C, default setting: 0..+50 °C, optionally configurable via App, uConfig or BUS |
Measuring range humidity | 0..100% rH non-condensing, enthalpy: 0..85 KJ/kg, absolute humidity: 0..50 | 0..80 g/m³, dew point: 0..+50 | -20..+80 °C, optionally configurable via app, uConfig or BUS |
Measuring range CO2 | 0..2000 ppm | 0..5000 ppm, optionally configurable via app, uConfig or BUS |
Accuracy temperature | ±0,5 K (typ. at 21 °C within default measuring range) |
Accuracy humidity | ±2% between 10..90% rH (typ. at 21 °C) |
Accuracy CO2 | ±50 ppm +3% of measured value (typ. at 21 °C, 50% rH, 1015 hPa) |
Sensor | VOC sensor (heated metal oxide semiconductor), CO2: NDIR (non-dispersive, infrared) |
Inputs | 1x input for floating contact |
Control functions | occupancy signalling, light ON/OFF/DIM, call scenarios, blinds UP/DOWN/SET, fan stages, setpoint, ECO function, showing measured value and history |
Display | TFT 3,5", 320x480 px |
Colour | Enclosure: pure white, black or aluminium, design cover: glass, white, black or aluminium, Operating elements same colour as enclosure |
Enclosure | enclosure NOVOS 7, PC V0, design cover pure white, black or aluminium |
Protection (IP) | IP30 according to EN 60529 |
Cable entry | rear entry, breaking points bottom, drill mark top |
Electrical connection | tool-free mountable spring clamp, max. 1,5 mm² |
Ambient condition | 0..+50 °C, max. 85% rH non-condensing |
Mounting | flush-mounted on standard EU box (Ø=60 mm), to be mounted flat onto the surface using adhesive foil or screws, base part can be mounted and wired separately |
Notes | mixed gas sensors detect gases and vapours which can be oxidised (burnt): Body odours, tobacco smoke, exhalations emitted by materials (furniture, carpets, paint, glue ...) |