The NOVOS 7 stands out for its well-known and intuitive user interface using a rotary push button and a 3.5" TFT display. Four favourite buttons allow quick access to frequently used functions such as temperature set point or light control. Blinds and lights can thus be configured accordingly. The NOVOS 7 can be equipped with up to 4 integrated sensors (temperature, relative humidity, CO2 and VOC) and contributes to a comfortable room ambience and energy savings.

Measured valuestemperature, humidity, CO2, VOC (depending on the device)
Network technologyRS485 Modbus
Power supply24 V = (±10%) or 24 V ~ (±10%) SELV
Power consumptiontyp. 2 W (24 V =)
Measuring range temp.-50..+50 °C | 0..+50 °C | -20..+80 °C | -15..+35 °C, default setting: 0..+50 °C, optionally configurable via App, uConfig or BUS
Measuring range humidity0..100% rH non-condensing, enthalpy: 0..85 KJ/kg, absolute humidity: 0..50 | 0..80 g/m³, dew point: 0..+50 | -20..+80 °C, optionally configurable via app, uConfig or BUS
Measuring range CO20..2000 ppm | 0..5000 ppm, optionally configurable via app, uConfig or BUS
Accuracy temperature±0,5 K (typ. at 21 °C within default measuring range)
Accuracy humidity±2% between 10..90% rH (typ. at 21 °C)
Accuracy CO2±50 ppm +3% of measured value (typ. at 21 °C, 50% rH, 1015 hPa)
SensorVOC sensor (heated metal oxide semiconductor), CO2: NDIR (non-dispersive, infrared)
Inputs1x input for floating contact
Control functionsoccupancy signalling, light ON/OFF/DIM, call scenarios, blinds UP/DOWN/SET, fan stages, setpoint, ECO function, showing measured value and history
DisplayTFT 3,5", 320x480 px
ColourEnclosure: pure white, black or aluminium, design cover: glass, white, black or aluminium, Operating elements same colour as enclosure
Enclosureenclosure NOVOS 7, PC V0, design cover pure white, black or aluminium
Protection (IP)IP30 according to EN 60529
Cable entryrear entry, breaking points bottom, drill mark top
Electrical connectiontool-free mountable spring clamp, max. 1,5 mm²
Ambient condition0..+50 °C, max. 85% rH non-condensing
Mountingflush-mounted on standard EU box (Ø=60 mm), to be mounted flat onto the surface using adhesive foil or screws, base part can be mounted and wired separately
Notesmixed gas sensors detect gases and vapours which can be oxidised (burnt): Body odours, tobacco smoke, exhalations emitted by materials (furniture, carpets, paint, glue ...)