NOVOS 5 x BUS
The surface-mounted NOVOS 5 x comes in the NOVOS design with an integrated temperature sensor. Possible operating elements are set point potentiometer, status LED with up to 7 selectable colors, rotary switch for fan stage control and a presence button. The connection terminal in the back part allows for separate pre-wiring. The device is furthermore available with an LCD and integrated traffic light indication for indicating the status of measured values. Threshold values and display settings can be individually configured using the Thermokon NOVOSapp.
Measured values | temperature, humidity, CO2, VOC (depending on the device) |
---|---|
Network technology | RS485 BACnet (MS/TP), RS485 Modbus |
Power supply | 15..35 V = or 19..29 V ~ SELV |
Power consumption | typ. 0,4 W (24 V =) | 0,8 VA (24 V ~) |
Measuring range temp. | -35..+70 °C |
Measuring range humidity | 0..100% rH non-condensing, enthalpy: 0..85 KJ/kg, absolute humidity: 0..50 | 0..80 g/m³, dew point: 0..+50 | -20..+80 °C, optionally configurable via app, uConfig or BUS |
Measuring range CO2 | 0..2000 ppm | 0..5000 ppm, optionally configurable via app, uConfig or BUS |
Accuracy temperature | ±0,5 K (typ. at 21 °C) |
Accuracy humidity | ±2% between 10..90% rH (typ. at 21 °C) |
Accuracy CO2 | ±50 ppm +3% of measured value (typ. at 21 °C, 50% rH, 1015 hPa) |
Calibration | CO2: Dual Channel, Automatic zero point calibration, VOC: self-calibration |
Inputs | 1x input for floating contact |
Setpoint (P) | potentiometer, depending on the device |
Rotary switch (S) | for fan stage adjustment (max. 5 stages), 5-stages (auto,0,I,II,III), 2-stages (0,I), 3-stages (0,I,II), 4-stages (0,I,II,III), depending on the device |
Button (T) | for presence detection, with LED (TD), depending on the device |
LED (D) | for status feedback, colour configurable via app, uConfig or BUS, depending on the device |
Display | LCD 29x35 mm with RGB backlight, optional, Display and colours optionally configurable via app, uConfig or BUS |
Colour | pure white, black or aluminium, Operating elements same colour as enclosure |
Enclosure | PC V0, design cover pure white, black or aluminium |
Protection (IP) | IP30 according to EN 60529 |
Cable entry | rear entry, breaking points bottom, drill mark top |
Electrical connection | tool-free mountable spring clamp, max. 1,5 mm² |
Ambient condition | -35..+70 °C, LCD: -20..+70 °C, max. 85% rH non-condensing |
Mounting | flush-mounted on standard EU box (Ø=60 mm), or to be mounted flat onto the surface using screws, base part can be mounted and wired separately |
Notes | mixed gas sensors detect gases and vapours which can be oxidised (burnt): Body odours, tobacco smoke, exhalations emitted by materials (furniture, carpets, paint, glue ...) |