NOVOS 3 x BUS

The surface-mounted NOVOS 5 x comes in the NOVOS design with an integrated temperature sensor and an RS485 Modbus interface. Possible operating elements are set point potentiometers, status LED with up to 7 selectable colors and presence buttons. The separate back part with its connection terminals allows pre-wiring. Threshold values can be individually configured using the Thermokon NOVOSapp.

Measured valuestemperature, humidity, CO2, VOC (depending on the device)
Network technologyRS485 BACnet (MS/TP), RS485 Modbus
Power supply15..35 V = or 19..29 V ~ SELV
Power consumptiontyp. 0,4 W (24 V =) | 0,8 VA (24 V ~)
Measuring range temp.-35..+70 °C
Accuracy temperature±0,5 K (typ. at 21 °C)
Accuracy humidity±2% between 10..90% rH (typ. at 21 °C)
Accuracy CO2±50 ppm +3% of measured value (typ. at 21 °C, 50% rH, 1015 hPa)
CalibrationCO2: Dual Channel, Automatic zero point calibration, VOC: self-calibration
Inputs1x input for floating contact
Setpoint (P)potentiometer, depending on the device
Button (T)for presence detection, with LED (TD), depending on the device
LED (D)for status feedback, colour configurable via app, uConfig or BUS, depending on the device
Colourpure white, black or aluminium, Operating elements same colour as enclosure
EnclosurePC V0, optionally with design cover black or aluminium
Protection (IP)IP20 according to EN 60529
Cable entryrear entry, breaking points bottom, drill mark top
Electrical connectiontool-free mountable spring clamp, max. 1,5 mm²
Ambient condition-35..+70 °C, max. 85% rH non-condensing
Mountingflush-mounted on standard EU box (Ø=60 mm), or to be mounted flat onto the surface using screws, base part can be mounted and wired separately
Notesmixed gas sensors detect gases and vapours which can be oxidised (burnt): Body odours, tobacco smoke, exhalations emitted by materials (furniture, carpets, paint, glue ...)