LCR Touch

Room operating unit with an integrated temperature sensor (rH sensor optional) and touch surface for visualization of the measured values and room control. It provides connection to an RS485 Modbus network and additional three inputs. The LCR Touch forms the basis for a pleasant indoor climate and well-being. Typical applications are schools, office buildings, hotels or cinemas. The intuitive operation offers all relevant HVAC functions for an intelligent and energy-saving room automation.

Measured valuestemperature, humidity
Network technologyRS485 Modbus
Power supply24 V = or 24 V ~ (±20%) SELV
Power consumptiontyp. 3 W (24 V =) | 5 VA (24 V ~)
Measuring range temp.0..+50 °C
Measuring range humidity0..100% rH non-condensing
Accuracy temperature±1 K (typ. at 21 °C)
Accuracy humidity±2% between 10..90% rH (typ. at 21 °C)
Inputs1x input digital for floating contact (window contact, dew point guard), 1x input digital for floating contact (motion sensors, card switch), 1x input for change-over sensor NTC10k
Control functionsfactory setting (+16..+30°C), setpoint 0..+50 °C
No. of buttons5
DisplayLCD 64x41 mm, backlight white
EnclosureABS, glass, pure white, Frame silver
Protection (IP)IP20 according to EN 60529
Electrical connectionterminal block, max. 1,5 mm²
Ambient condition-10..+50 °C, max. 85% rH short term condensation
Mountingflush-mounted in standard EU box (Ø=60 mm, min. depth=45 mm)
Contact

Contact us:


Thermokon Sensortechnik GmbH
Platanenweg 1
35756 Mittenaar
Tel.: +49 2778 6960-0


Write email


View contact