WRF07 RR

The flush-mounted room unit with set point adjustment provides ambient temperature and set point in living spaces, hotel and office rooms. The WRF07 can be used with most common switch ranges and is furthermore available in various colors. It is especially suited for design-oriented buildings. The removable terminals allow for pre-wiring. The WRF07 can be connected through RS485 Modbus or LON to a superior BMS.

Measured valuestemperature, humidity, depending on the device
Output voltageAO2V: 2x 0..10 V
Network technologyLON FT (free topology), RS485 Modbus, RS485 BACnet (MS/TP)
Power supply15..24 V = (±10%) or 24 V ~ (±10%) SELV
Power consumptiontyp. 1 W (24 V =) | 2,5 VA (24 V ~)
Measuring range temp.0..+50 °C
Measuring range humidity0..100% rH non-condensing
Accuracy temperature±0,5 K (typ. at 21 °C)
Accuracy humidity±2% between 10..90% rH (typ. at 21 °C)
InputsAO2V: 2 inputs, floating switch contact, DI4: 4x input digital for floating switch contact
Switch range BerkerS.1, B.3 aluminum, B.7 glass, Q.1, Q.3, K.5 aluminum | stainless steel
Switch range Busch-JaegerBusch-balance® SI, Busch-Duro 2000® SI, Reflex SI, solo®, future® linear, impuls, Busch-axcent®, alpha nea®
Switch range FellerEDIZIOdue
Switch range GiraE2, E3, Standard 55, Esprit, Event, F100
Switch range JungLS 990, A 500, AS 500, A plus, A creation, CD 500
Switch range MertenM-Smart, M-Plan, 1-M, Atelier-M, M-Pure, Artec, Artec stainless steel, Antik
Switch range PehaAURA, AURA glass
Setpoint (P)potentiometer
Button (T)for presence detection, for fan stage adjustment (depending on the device)
LED (D)for status feedback, green (standard), several LEDs possible (e.g. green, yellow, red)
EnclosureCentral disc in switch manufacturer's design (appearance may vary)
Protection (IP)IP20 according to EN 60529
Electrical connectionterminal block, max. 1,5 mm²
Ambient condition0..+50 °C, max. 85% rH non-condensing
Mountingflush-mounted in standard EU box (Ø=60 mm, min. depth=45 mm), DO2T, DO2R, OVR, OVT with IO extension need 2 flush-mounting boxes (Ø=60 mm) and double frame (alternatively, the IO unit can be mounted in a deep flush-mounted box or be detached up to 10 m)
Delivery contentsoftware for configuration (freeware via download)
Notesfor further variants see chapter room operating units, for other operating elements please request, for other frame designs please request
Rocker switch (S)for fan speed adjustment
Contact

Contact us:


Thermokon Sensortechnik GmbH
Platanenweg 1
35756 Mittenaar
Tel.: +49 2778 6960-0


Write email