WRF06 LCD RR
The flush-mounted room controller with set point adjustment, fan stage control and occupancy button is used for individual temperature control in living spaces, hotel and office rooms. The WRF06 LCD with its 4 push buttons and an integrated LCD can be used with most common switch ranges and is furthermore available in various colors. It is especially suited for design-oriented buildings. Depending on the type, proportional 0..10 V and 6-way valves for heating/ cooling can be controlled. The removable terminals allow for pre-wiring. The WRF06 LCD can be connected through RS485 Modbus or LON to a superior BMS.
Measured values | temperature |
---|---|
Output voltage | AO2V: 2x 0..10 V |
Network technology | LON FT (free topology), RS485 Modbus |
Power supply | 15..24 V = (±10%) or 24 V ~ (±10%) SELV |
Power consumption | RS485 Modbus: typ. 0,8 W (24 V =) | 2,5 VA (24 V ~), LON: typ. 1,3 W (24 V =) | 1,5 VA (24 V ~) |
Measuring range temp. | 0..+50 °C |
Accuracy temperature | ±0,5 K (typ. at 21 °C) |
Inputs | floating switch contact |
Switch range Berker | S.1, B.3 aluminum, B.7 glass |
Switch range Busch-Jaeger | Busch-balance® SI, solo® *, future® linear *, Busch-axcent® * |
Switch range Feller | EDIZIOdue |
Switch range Gira | E2, E3, Standard 55, Esprit, Event, F100 * |
Switch range Jung | LS 990 *, A 500, AS 500, A plus, A creation, CD 500 * |
Switch range Merten | M-Smart, M-Plan, 1-M, Atelier-M, M-Pure, Artec *, Antik * |
Switch range Peha | AURA, AURA glass |
Functions | AO2V: 2 inputs, 2 outputs 0..10 V, DO2R: 2 inputs, 2 outputs relay, DO2T: 2 inputs, 2 outputs Triac, OVR: 2 inputs, 2 outputs (1x 0..10 V, 1 relay), OVT: 2 inputs, 2 outputs (1x 0..10 V, 1 Triac) |
No. of buttons | 4 |
Display | LCD 34x21 mm, monochrome |
Enclosure | PC, pure white brilliant, pure white matt, aluminium, anthracite, frame color may differ slightly |
Protection (IP) | IP30 according to EN 60529 |
Electrical connection | terminal block, max. 1,5 mm², pluggable |
Ambient condition | 0..+50 °C, max. 85% rH non-condensing |
Mounting | flush-mounted in standard EU box (Ø=60 mm, min. depth=45 mm), DO2T, DO2R, OVR, OVT with IO extension need 2 flush-mounting boxes (Ø=60 mm) and double frame (alternatively, the IO unit can be mounted in a deep flush-mounted box or be detached up to 10 m) |
Delivery content | software for configuration (freeware via download) |
Notes | for further variants see chapter room operating units, * in switch program with intermediate frame, please specify frame design when ordering, please indicate labelling type in order, BUS: only available with labelling type 1 and 2 |