JOY Fancoil

The fancoil controller in high-quality design is used for individual temperature control in hotels, offices and living spaces. It is designed for fan coil units with 2- and 4-pipe systems. Different fans can be controlled depending on the version (type 5DO for 3-stage and type EC for 0..10 V fan). By means of type EC 3AO continuous valve actuators (also 6-way valve) and a 0..10 V EC motor can be controlled. This ensures individual and energy-efficient room air conditioning. The device (available with glass front in white or black) has a display and touch-sensitive control buttons. You can set 3 time channels with 4 time periods each. The device is designed for mounting in a flush-mounted box.

Measuring values temperature
Output voltage types AO2DO: 0..10 V = (to control EC fan), types 3AO: 3x 0..10 V = (to control EC fan, heating & cooling or to control 6-way control valve)
Output switch contact types 5DO: 5x contact NO (1x heating, 1x cooling, 3x fan stages), types AO2DO: 2x contact NO (1x heating, 1x cooling)
Network technology RS485 Modbus
Power supply 85..260 V ~, types 3AO: 15..24 V = (±10%) or 24 V ~ (±10%) SELV
Power consumption max. 2 VA (260 V ~)
Measuring range temp. 0..+50 °C
Accuracy temperature ±1 K (typ. at 21 °C)
Inputs 1x input for NTC10k or floating contact, 1x input digital for floating contact (not types BUS), input change-over (230 V ~), 3AO: instead of input change-over (230 V ~) additional input digital for floating contact
Control functions setpoint 0..+50 °C
Functions integrated PI and two-/three-position controller, types 3AO: built-in PI controller
Display LCD 60x44 mm, 240x160 px, backlight blue
Enclosure PC, pure white, black, hardened acrylic glass with high scratch resistance
Protection IP30 according to EN 60529
Connection electrical terminal block, max. 1,5 mm², inputs: terminal block, max. 1,0 mm²
Ambient condition 0..+50 °C, max. 85% rH non-condensing
Weight 195 g
Mounting flush mounted in standard EU box (Ø=60 mm, min. depth=45 mm), hollow wall boxes with edge Ø>70 mm have to be covered by wall covering
Contact

Contact us:


Thermokon Sensortechnik GmbH
Platanenweg 1
35756 Mittenaar
Tel.: +49 2778 6960-0


Write email