WRF06 LCD

Room and space temperature measurement with set point adjustment, fan speed, LCD display and manual override. Integrated heating/cooling controller and digital inputs for window contacts, dew point detection and analogue, relay or triac outputs for control valves. Available as a standalone or LON or Modbus communications. Fits into switch frames 55x55 mm.

Measuring valuestemperature
Output voltageVV: 2x 0..10 V
Network technologyLON FT (free topology), RS485 Modbus
Power supply15..24 V = (±10%) or 24 V ~ (±10%)
Power consumptionVV | RS485 Modbus: typ. 0,8 W (24 V =) | 2,5 VA (24 V ~), LON: typ. 1,3 W (24 V =) | 1,5 VA (24 V ~)
Measuring range temp.0..+50 °C
Accuracy temperature±0,5 K (typ. at 21 °C)
Inputsfloating switch contact
Switch range BerkerS.1, B.3 aluminum, B.7 glass
Switch range Busch-JaegerBusch-balance® SI, solo®, future® linear, Busch-axcent®
Switch range FellerEDIZIOdue
Switch range GiraE2, E3, Standard 55, Esprit, Event, F100
Switch range JungLS 990, A 500, AS 500, A plus, A creation, CD 500
Switch range MertenM-Smart, M-Arc, M-Plan, 1-M, Atelier-M, M-Pure, Artec, Antique
Switch range PehaAURA, AURA glass
FunctionsVV: 2 inputs, 2 outputs 0..10 V temperature/set point, AO2V: 2 inputs, 2 outputs 0..10 V, DI4: 4 inputs (digital), DO2R: 2 inputs, 2 outputs relay, DO2T: 2 inputs, 2 outputs Triac, OVR: 2 inputs, 2 outputs (1x 0..10 V, 1 relay), OVT: 2 inputs, 2 outputs (1x 0..10 V, 1 Triac)
No. of buttons4
DisplayLCD 34x21 mm, monochrome
EnclosurePC, pure white, aluminium, anthracite
ProtectionIP30 according to EN 60529
Connection electricalterminal block, max. 1,5 mm², pluggable
Ambient condition0..+50 °C, max. 85% rH non-condensing
Mountingflush mounted in standard EU box (Ø=55 mm), DO2T, DO2R, OVR, OVT with IO extension need 2 flush-mounting boxes (Ø=55 mm) and double frame (1 deep flush-mounting box Ø=55 mm may be used)
Delivery contentssoftware for configuration (freeware via download)
Notesfor devices measuring temperature and humidity digitalSTROM please look at FTW06 LCD (category Humidity), please specify frame design when ordering, please indicate labelling type in order, VV: only available with labelling type 1 and 3, BUS: only available with labelling type 1 and 2