NOVOS 5 rH

Room sensor with LCD for measuring relative and absolute humidity, enthalpy, dew point and temperature. The maintenance-free sensor is especially designed for schools, office buildings, hotels, cinemas and similar applications. Threshold values and display settings can be individually configured via Thermokon NOVOSapp. For models with set point and fan stage adjustment, please refer to the 'NOVOS 5 x' model in the chapter 'Room Operating Units'.

Measured valueshumidity, temperature
Output voltageVV: 2x 0..10 V or 0..5 V, (live-zero configuration via app or uConfig), max. load 10 kΩ
Output currentAA: 2x 4..20 mA, max. load 500 Ω
Network technologyRS485 BACnet (MS/TP), RS485 Modbus
Power supply15..35 V = or 19..29 V ~ SELV, A: 15..35 V = SELV
Power consumptiontyp. 0,6 W (24 V =) | 1,0 VA (24 V ~)
Operating temperature range-20..+70 °C
Measuring range humidity0..100% rH non-condensing, enthalpy: 0..85 KJ/kg, absolute humidity: 0..50 | 0..80 g/m³, dew point: 0..+50 | -20..+80 °C, optionally configurable via app, uConfig or BUS
Accuracy temperature±0,5 K (typ. at 21 °C)
Accuracy humidity±2% between 10..90% rH (typ. at 21 °C)
InputsRS485 Modbus:, 1x input for floating contact
DisplayLCD 29x35 mm with RGB backlight, Display and colours optionally configurable via app, uConfig or BUS
Colourpure white, black or aluminium
EnclosurePC V0, design cover pure white, black or aluminium
Protection (IP)IP30 according to EN 60529
Cable entryrear entry, breaking points bottom, drill mark top
Electrical connectiontool-free mountable spring clamp, max. 1,5 mm²
Ambient conditionmax. 85% rH non-condensing
Mountingflush-mounted on standard EU box (Ø=60 mm), or to be mounted flat onto the surface using screws, base part can be mounted and wired separately
Notesfor configuration an optional programming dongle (Bluetooth) is available (refer to accessories)
Contact

Contact us:


Thermokon Sensortechnik GmbH
Platanenweg 1
35756 Mittenaar
Tel.: +49 2778 6960-0


Write email