FTB+
Wall-mounted sensor for measuring relative humidity and temperature in a high quality and inconspicious stainless steel design. For plastering into flush-mounted boxes or installations in hollow walls. Especially designed for museums and exhibitions, where measuring accuracy and almost invisible sensors have to be installed due to architectural design. The precise measurements provided to a BMS system contribute to a comfortable room climate and prevent mold formation.
Measured values | humidity, temperature |
---|---|
Output voltage | VV: 2x 0..10 V or 0..5 V (adjustable via jumper), min. load 10 kΩ |
Output current | AA: 2x 4..20 mA, max. load 500 Ω |
Power supply | 15..24 V = (±10%) or 24 V ~ (±10%) SELV, AA: 15..24 V = (±10%) SELV |
Power consumption | AA: max. 1 W (24 V =) |
Measuring range temp. | -40..+60 °C | 0..+50 °C | -20..+80 °C | -15..+35 °C, adjustable at the transducer, default setting: -20..+80 °C |
Measuring range humidity | 0..100% rH non-condensing, enthalpy: 0..85 KJ/kg, absolute humidity: 0..50 | 0..80 g/m³, dew point: 0..+50 | -20..+80 °C, adjustable at the transducer |
Accuracy temperature | ±0,3 K (typ. at 21 °C within default measuring range) |
Accuracy humidity | ±2% between 10..90% rH (typ. at 21 °C) |
Enclosure | enclosure USE-M, PC, pure white |
Protection (IP) | enclosure: IP65 according to EN 60529 |
Cable entry | Flextherm M20 for wire Ø=4,5..9 mm, removable |
Electrical connection | removable plug-in terminal, max. 2,5 mm², sensor wire PVC 15 m |
Sensor head | stainless steel V2A, Ø=13 mm, length=34,4 | 66,4 mm |
Ambient condition | -35..+70 °C, sensor: -40..+120 °C, max. 85% rH short term condensation |
Delivery content | incl. mounting base enclosure USE-M pure white |