Weatherproof humidity and temperature sensor for outdoor applications. The radiation shield protects the sensors from rain, hail and radiated heat. The curved shape of the plates ensure that air can move across the sensors to keep radiated temperature from rooftops and other surrounding surfaces away and guarantee proper measurement. Typical applications are meteorology, greenhouses and industrial environments.

Measured valueshumidity, temperature
Output voltageVV: 2x 0..10 V, min. load 10 kΩ
Output currentAA: 2x 4..20 mA, max. load 500 Ω
Network technologyRS485 BACnet (MS/TP), LON FT (free topology), RS485 Modbus
Power supply15..24 V = (±10%) or 24 V ~ (±10%) SELV, AA: 15..24 V = (±10%) SELV, BUS: 15..35 V = or 19..29 V ~ SELV
Power consumptionmax. 2,5 W (24 V =) | 4,3 VA (24 V ~), VV: max. 0,4 W (24 V =) | 0,8 VA (24 V ~), AA: max. 1 W (24 V =)
Measuring range temp.-40..+60 °C | 0..+50 °C | -20..+80 °C | -15..+35 °C, VV | AA: adjustable at the transducer, default setting: -20..+80 °C
Measuring range humidity0..100% rH non-condensing, enthalpy: 0..85 KJ/kg, absolute humidity: 0..50 | 0..80 g/m³, dew point: 0..+50 | -20..+80 °C, optionally configurable via app or uConfig
Accuracy temperature±0,3 K (typ. at 21 °C within default measuring range)
Accuracy humidity±2% between 10..90% rH (typ. at 21 °C)
Enclosureenclosure USE-S, BUS:, enclosure USE-M, PC, pure white
Protection (IP)IP65 according to EN 60529
Cable entryFlextherm M20 for wire Ø=4,5..9 mm, BUS: M25 with fourfold cable entry for wire with max. Ø=7 mm, removable
Electrical connectionremovable plug-in terminal, max. 2,5 mm², BUS terminal: removable plug-in terminal, max. 1,5 mm²
PipePA6, black, Ø=19,5 mm
Filterstainless steel wire mesh
Ambient condition-20..+70 °C, max. 85% rH short term condensation
Mountingmounting at the wall or at a pole