FSR01
Hygrostat for ON/OFF control of ventilation and air conditioning, humidification and dehumidification equipment in rooms and office spaces, data centers, warehouses and similar applications.
Measured values | humidity |
---|---|
Medium | air |
Output switch contact | changeover contact, floating, dehumidify, max. 250 V, 5 (1) A, min. 100mA, humidify, max. 250 V, 3 (1) A, min. 100mA |
Measuring range humidity | 30..100% rH non-condensing |
Working range humidity | 35..95% rH |
Accuracy humidity | ±3% rH (typ. at 50% rH), average temperature coefficient -0,2% / K, typ at 20 °C, 50% rH |
Sensor | Polyga® measuring element, water resistant, washable |
Enclosure | PC, pure white |
Protection (IP) | IP30 according to EN 60529 |
Cable entry | breaking points top/bottom, rear entry |
Electrical connection | terminal block, max. 1,5 mm² |
Ambient condition | 0..+60 °C |
Weight | 60 g |
Mounting | flush-mounted on standard EU box (Ø=60 mm), to be mounted flat onto the surface using adhesive foil or screws, with frame for surface mounting (accessory) or directly on the wall, base part can be mounted and wired separately |
Notes | threshold adjustment via potentiometer or internal adjuster |