FTK+ relay / LCD / BUS

Duct sensor for measuring relative and absolute humidity, enthalpy, dew point and temperature in gaseous media of heating, ventilation and air-conditioning systems as well as in clean room technology. The devices with relay output for a 2-point controller or a 2-stage 2-point controller and color-changing LCD allow a wide range of applications. Depending on the model, the sensor can be individually configured via Thermokon USEapp. Accuracy of the humidity sensor is 2%. Tool-free opening, closing and wiring as well as removable cable entries ensure quick and easy installation.

Measuring values humidity, temperature
Output voltage 2x 0..10 V or 0..5 V (adjustable via jumper; live-zero configuration via Thermokon USEapp), min. load 10 kΩ
Output ampere AA: 2x 4..20 mA, max. load 500 Ω
Output switch contact Relay: 2x floating contact NO for 24 V ~ or 24 V = / 3 A, optional
Network technology RS485 BACnet (MS/TP), RS485 Modbus
Power supply 15..35 V = or 19..29 V ~ SELV, AA: 15..35 V = SELV
Power consumption max. 2,5 W (24 V =) | 4,3 VA (24 V ~)
Measuring range temp. -40..+60 °C | 0..+50 °C | -20..+80 °C | -15..+35 °C, adjustable at the transducer, default setting: -20..+80 °C
Measuring range humidity 0..100% rH non-condensing, enthalpy: 0..85 KJ/kg, absolute humidity: 0..50 | 0..80 g/m³, dew point: 0..+50 | -20..+80 °C, adjustable at the transducer, optionally configurable via Thermokon USEapp
Accuracy temperature ±0,3 K (typ. at 21 °C within default measuring range)
Accuracy humidity ±2% between 10..90% rH (typ. at 21 °C)
Air speed max. 12 m/s
Display LCD 29x35 mm with RGB backlight, optional
Enclosure enclosure USE-M, PC, pure white, LCD: cover PC, transparent, with removable cable entry
Protection IP65 according to EN 60529
Cable entry Flextherm M16 for wire Ø=3..7 mm, Relay/BUS: M25 with fourfold cable entry for wire with max. Ø=7 mm, removable
Connection electrical removable plug-in terminal, max. 2,5 mm², BUS terminal: removable plug-in terminal, max. 1,5 mm²
Pipe PA6, black, Ø=19,5 mm, length 140 | 270 | 400 mm
Filter stainless steel wire mesh
Ambient condition -20..+70 °C, max. 85% rH short term condensation
Delivery contents incl. mounting flange