WK02+
Condensation sensor with an LED signal and a relay output to prevent condensation on chilled surfaces. For control and monitoring applications or connection to cooling valves to stop the flow of chilled water flow upon condensation. The 'ext.' model uses a 2m remote sensor for a more flexible installation.
Measured values | humidity, temperature, Conductivity |
---|---|
Output voltage | 2x 0..10 V or 0..5 V (adjustable via jumper; live-zero configuration via app or uConfig) |
Output switch contact | changeover contact, 24 V: max. 24 V / 1,0 A (resistive, floating), 230 V: max. 230 V ~ / 0,5 A (resistive, floating) |
Power supply | 24 V: 15..24 V = (±10%) or 24 V ~ (±10%) SELV, 230 V: 230 V ~ (±10%) |
Power consumption | 24 V: typ. 0,8 W (24 V =) | 1,6 VA (24 V ~), 230 V: typ. 3,5 VA |
Measuring range humidity | 0..100% rH non-condensing, enthalpy: 0..85 KJ/kg, absolute humidity: 0..50 | 0..80 g/m³, dew point: 0..+50 | -20..+80 °C, optionally configurable via app or uConfig |
Accuracy temperature | ±0,5 K (typ. at 21 °C within default measuring range) |
Accuracy humidity | ±2% between 10..90% rH (typ. at 21 °C) |
Display | LED green – power supply OK, LED red – condensation |
Enclosure | enclosure USE-L, PC, pure white, cover PC, transparent |
Protection (IP) | IP65 according to EN 60529 |
Cable entry | Flextherm M20 for wire Ø=4,5..9 mm, BUS: M25 with fourfold cable entry for wire with max. Ø=7 mm, removable |
Electrical connection | removable plug-in terminal, max. 2,5 mm² |
Ambient condition | 0..+50 °C, max. 85% rH short term condensation |
Delivery content | 1x syringe with terminal contact fluid, incl. mounting base enclosure USE-L pure white |
Notes | other cable lengths on request |