LS02+
Leakage detector with relay output and two signalling LEDs designed for alarm, control and monitoring applications of containers, false floors, suspended ceilings or rooms for preventing unintended ingress of water. The sensor can be adjusted to different heights so that the response time of the sensor can be adapted to the water level that is to be detected.
Measured values | Conductivity |
---|---|
Output switch contact | changeover contact, 24 V: max. 24 V / 1,0 A (resistive, floating) |
Power supply | 15..24 V = (±10%) or 24 V ~ (±10%) SELV |
Power consumption | typ. 0,6 W (24 V =) | 1,5 VA (24 V ~) |
Display | LED green – power supply OK, LED red – alarm, humidity detected |
Enclosure | enclosure USE-S, PC, pure white, cover PC, transparent |
Protection (IP) | IP65 according to EN 60529 |
Cable entry | Flextherm M20 for wire Ø=4,5..9 mm, removable |
Electrical connection | removable plug-in terminal, max. 2,5 mm² |
Ambient condition | -35..+90 °C, max. 85% rH short term condensation |
Mounting | Level compensation by adjustable contacts |
Notes | LS02+ ext.: with external sensor (L=5 m), Height/response behaviour can be changed via a conical spiral on the sensor element |