thanos SR

The wireless touch room operating unit is used for temperature and humidity measurement (optional) as well as for integrated operation of HVAC, lighting, blinds and other switching options in individual room control. Due to the bidirectional communication and the permanent power supply the thanos can communicate directly with EasySens® actuators SAB+/SAB05 and build up a control management. Additionally thanos has a clock with a shift schedule for setting comfort times. Due to the high-quality optics, the device is particularly suitable for design-oriented facilities. The operating functions can be flexibly used depending on the room requirement.

Measuring valuestemperature, humidity, depending on the device
Network technologyLON FT (free topology), RS485 Modbus
Radio technologyEnOcean (IEC 14543-3-10)
Frequency868 MHz, optional:, 902 MHz (Americas)
Data transmissionairConfig ready, all types without BUS
Power supply15..24 V = (±10%) or 24 V ~ (±10%) SELV, 240 V: 100..240 V ~
Power consumptiontyp. 2,0 W (24 V =) | 4,0 VA (24 V ~)
Measuring range temp.0..+50 °C
Measuring range humidity0..100% rH non-condensing
Accuracy temperature±0,5 K (typ. at 21 °C)
Accuracy humidity±3% between 20..80% rH (typ. at 21 °C)
Inputsindividual configuration for window contact, dew point guard, key card switch, room frequency, alarm, event, 24 V / RS485 Modbus: 4x digital
Control functionsoccupancy signalling, light ON/OFF/DIM, setup scenarios, blinds UP/DOWN/SET, fan stages, setpoint
Clipanodized aluminium
No. of buttonstype L/LQ min. 8 capacitive touch sensor buttons
Labellingtype L/LQ flexible insert (for up to 8 touch buttons below/beside clip)
DisplayTFT 3,5", 320x240 px, capacitive touch technology, showing room temperature, setpoint, operation mode, fan stage, occupancy, alarm, date and time, ..., ECO note (several steps, red to green; not available for LON), graphic and photo: Instead of date and time individual colour graphics (175x50 or 240x320 pixel) can be shown (e.g. company logo or hotel name; not available for LON),
Colourwhite or black
EnclosurePC and glass
ProtectionIP20 according to EN 60529
Connection electricalterminal block, max. 1,5 mm²
Ambient condition0..+50 °C, max. 85% rH non-condensing
Weighttype S/SQ: 300 g, type L/LQ: 400 g
Mountingflush-mounting in standard EU box (Ø=60 mm, min. depth=45 mm)
Delivery contentssoftware for configuration (freeware via download)
Notesyou'll find the software description at www.thermokon.com, to use the free software airConfig (download) a USB stick, which is able to send and receive EnOcean telegrams, is necessary. The EnOcean USB stick (incl. license) is included in airScan (item No. 566704 for 868 MHz)