SR07 x

Energy-harvesting design room operating unit for integrated measurement of temperature and relative humidity (rH version) in living and office spaces. Also available with slide switch (for example "Day/Night") or occupancy button. The device sends its values unidirectionally to corresponding receivers or gateways, which process the information directly or – depending on the application – forward it to a central control unit. The device to be mounted via adhesive pad or screws can be integrated in almost all 55x55 mm switch ranges. This allows to choose from many high quality designs.

Measuring values temperature, humidity, (optional)
Radio technology EnOcean (IEC 14543-3-10)
Frequency 868 MHz
Power supply solar cell, internal super cap, maintenance-free, optional: backup battery CR1632
Measuring range temp. 0..+40 °C
Measuring range humidity 0..100% rH non-condensing
Accuracy temperature ±0,4 K (typ. at 21 °C)
Accuracy humidity ±5% between 30..70% rH (typ. at 21 °C)
Measuring intervall WakeUp time = 100 sec. (default)
Transmission interval every 100 sec. at change >0,8 K or >1,6% rH, otherwise every 1000 sec.
Switch range Berker S.1, B.7 glass
Switch range Busch-Jaeger Busch-balance® SI, solo® *, future® linear *, Busch-axcent® *
Switch range Feller EDIZIOdue
Switch range Gira E2, E3, Standard 55, Esprit, Event, Flächenschalter *
Switch range Jung A 500, AS 500, A plus, A creation
Switch range Merten M-Smart, M-Plan, M-Pure
Set point (P) potentiometer
Slide switch (MS) I/0, day/night
Button (T) for presence detection
Protection IP20 according to EN 60529
Ambient condition -25..+65 °C, max. 85% rH non-condensing
Weight 45 g
Mounting to be mounted flat onto the surface using adhesive foil (included) or screws
Delivery contents adhesive foil
Notes * in switch program with intermediate frame, integrated coin cell backup possibility for usage in dark rooms