SR06 LCD

Bidirectional and energy self-sufficient room operating unit with sensors for detection of temperature and relative humidity (rh type). Depending on the different types available, parameters such as temperature set point, fan stage or room occupancy can be set via the function buttons at the device. SR06 LCD transmits the measuring values to a receiver that directly processes the information received. According to the SR06 LCD type and application used, the values can be forwarded to a central control unit. By means of SmartACK set points and status can be overwritten externally and indicated via the integrated display. Parameterization is done via radio using airConfig or by the optional configuration software (see accessories).

Measuring valuestemperature, humidity, (optional)
Radio technologyEnOcean (IEC 14543-3-10)
Frequency868 MHz, optional:, 902 MHz (Americas)
Data transmissionbidirectional, SmartACK (SmartACKNOWLEDGE), airConfig ready
Power supplysolar cell, LiPo-battery, maintenance-free
Measuring range temp.0..+40 °C
Measuring range humidity0..100% rH non-condensing
Accuracy temperature±0,4 K (typ. at 21 °C)
Accuracy humidity±5% between 30..70% rH (typ. at 21 °C)
Measuring intervallWakeUp time = 100 sec. (default), heartbeat cycle = every 10th wakeup, configured via airConfig or SR06ConfigSW
Switch range BerkerS.1, B.7 glass
Switch range Busch-JaegerBusch-balance® SI, solo®, future® linear, Busch-axcent®
Switch range FellerEDIZIOdue
Switch range GiraE2, E3, Standard 55, Esprit, Event, F100
Switch range JungA 500, AS 500, A plus, A creation
Switch range MertenM-Smart, M-Arc, M-Plan, M-Pure
Control functionsoccupancy signalling, fan stages, setpoint
No. of buttons2T: 2 buttons, 4T: 4 buttons
DisplayLCD 29x12 mm, monochrome
Set point range+15..+30 °C ±10 °C
EnclosurePC, pure white, aluminium, anthracite
ProtectionIP20 according to EN 60529
Ambient condition-25..+65 °C
Weight50 g
Mountingto be mounted flat onto the surface using adhesive foil (included) or screws
Notesintegrated coin cell backup possibility for usage in dark rooms, for configuration an optional programming interface is necessary (refer to accessories), energy storage can be reloaded with a separate USB-cable, to use the free software airConfig (download) an usb stick, which is able to send and receive EnOcean telegrams, is necessary. We offer such a stick with the package airScan (item No. 566704 for 868 MHz)