SR06 LCD

Energy-harvesting design room control unit for integrated measurement of temperature and relative humidity (rH version). Depending on version and type, temperature setpoint, fan levels, room occupancy, lighting or blinds can be adjusted or switched via the buttons on the device. The device sends its measured values ​​to corresponding receivers or gateways, which process the information directly or – depending on the application – forward it to a central control unit. Using the SmartACKNOWLEDGE Protocol, setpoint, fan level and room occupancy of the bidirectionally operating wireless room operating unit can be externally overwritten and shown in the integrated display. The room control unit is parameterised via radio using airConfig software or alternatively via the optionally available USB programming interface. By using this interface the energy storage can be additionally charged. The device, mounted via adhesive pads or screws, can be integrated into most 55x55 mm switch ranges. This allows to choose from many high quality designs.

Measuring values temperature, humidity, (optional)
Radio technology EnOcean (IEC 14543-3-10)
Frequency 868 MHz, optional:, 902 MHz (Americas)
Data transmission bidirectional, SmartACK (SmartACKNOWLEDGE), airConfig ready
Power supply solar cell, LiPo-battery, maintenance-free
Measuring range temp. 0..+40 °C
Measuring range humidity 0..100% rH non-condensing
Accuracy temperature ±0,4 K (typ. at 21 °C)
Accuracy humidity ±5% between 30..70% rH (typ. at 21 °C)
Measuring intervall WakeUp time = 240 sec. (default), heartbeat cycle = every 10th wakeup, optionally configurable via airConfig or SR06ConfigSW
Switch range Berker S.1, B.7 glass
Switch range Busch-Jaeger Busch-balance® SI, solo® *, future® linear *, Busch-axcent® *
Switch range Feller EDIZIOdue
Switch range Gira E2, E3, Standard 55, Esprit, Event, F100 *
Switch range Jung A 500, AS 500, A plus, A creation
Switch range Merten M-Smart, M-Plan, M-Pure
Control functions occupancy signalling, fan stages, setpoint
No. of buttons 2T: 2 buttons, 4T: 4 buttons
Display LCD 29x12 mm, monochrome
Set point range +15..+30 °C ±1..10 °C, optionally configurable via airConfig or SR06ConfigSW
Enclosure PC, pure white, aluminium, anthracite
Protection IP20 according to EN 60529
Ambient condition 0..+40 °C
Weight 50 g
Mounting to be mounted flat onto the surface using adhesive foil (included) or screws
Notes * in switch program with intermediate frame, integrated coin cell backup possibility for usage in dark rooms, for configuration an optional programming interface is available (refer to accessories), energy storage can be recharged with a separate USB-cable, to use the free software airConfig (download) a USB stick, which is able to send and receive EnOcean telegrams, is necessary. The EnOcean USB stick (incl. license) is included in airScan (item No. 566704 for 868 MHz)
Contact

Contact us:


Thermokon Sensortechnik GmbH
Platanenweg 1
35756 Mittenaar
Tel.: +49 2778 6960-0


Write email


View contact