SR06 LCD

Energy-harvesting wireless room operating unit with an integrated LCD for the measurement of temperature and relative humidity (rH version). Depending on the type, temperature set point, fan stages, room occupancy, lighting or blinds can be controlled using the operating buttons on the device. The device transmits its measured values to corresponding receivers or gateways, which directly process the information or - depending on the application - forward it to a BMS controller. Using the SmartACK protocol, the bidirectional communication is capable of managing a local overwrite from BMS of e.g. set point, fan stages and room occupancy. The SR06 LCD can be wirelessly parameterized by using the airConfig software or alternatively through the optional USB programming interface. Although the SR06 LCD is a self-powered device, the energy capacitor of the device can also be charged via USB interface if required. It can be integrated into almost any 55x55 mm frames, allowing you to choose from many designs and frame manufacturers. The SR06 LCD is mounted by using the adhesive pad or screws.

Measured valuestemperature, humidity, depending on the device
Radio technologyEnOcean (IEC 14543-3-10)
Frequency868 MHz, optional:, 902 MHz (Americas)
Data transmissionbidirectional, SmartACK (SmartACKNOWLEDGE), airConfig ready
Power supplysolar cell, LiPo-battery, maintenance-free, optional: backup battery CR1632
Measuring range temp.0..+40 °C
Measuring range humidity0..100% rH non-condensing
Accuracy temperature±0,4 K (typ. at 21 °C)
Accuracy humidity±5% between 30..70% rH (typ. at 21 °C)
Measurement intervalWakeUp time = 240 sec. (default), heartbeat cycle = every 10th wakeup, optionally configurable via airConfig or SR06ConfigSW
Switch range BerkerS.1, B.7 glass
Switch range Busch-JaegerBusch-balance® SI, solo® *, future® linear *, Busch-axcent® *
Switch range FellerEDIZIOdue *
Switch range GiraE2, E3, Standard 55, Esprit, Event, F100 *
Switch range JungA 500, AS 500, A plus, A creation
Switch range MertenM-Smart, M-Plan, M-Pure
Control functionsoccupancy signalling, fan stages, setpoint
No. of buttons2T: 2 buttons, 4T: 4 buttons
DisplayLCD 29x12 mm, monochrome
Setpoint range+15..+30 °C ±1..10 °C, optionally configurable via airConfig or SR06ConfigSW
EnclosurePC, pure white brilliant, aluminium, Jung aluminium (suitable for switch ranges Jung), anthracite
Protection (IP)IP20 according to EN 60529
Ambient condition0..+40 °C
Weight50 g
Mountingto be mounted flat onto the surface using adhesive foil (included) or screws
Notes* in switch program with intermediate frame, integrated coin cell backup possibility for usage in dimly lit rooms, for configuration an optional programming interface is available (refer to accessories), energy storage can be recharged with a separate USB-cable, to use the free software airConfig (download) a USB stick, which is able to send and receive EnOcean telegrams, is necessary. The EnOcean USB stick (incl. license) is included in airScan (item No. 566704 for 868 MHz)
Contact

Contact us:


Thermokon Sensortechnik GmbH
Platanenweg 1
35756 Mittenaar
Tel.: +49 2778 6960-0


Write email