JOY SR HC

The 24 V supplied type 3AO has three 0..10 V outputs for controlling heating/cooling valves or a 6-way valve. The 230 V supplied type AO2DO controls the 230 V heating and cooling valve as a 2-point or thermal 230 V actuator via PWM. The analog output is also used to control a 6-way valve. Two configurable inputs can be used as sensor input, room occupancy or energy lock. In addition to wired valve drives and sensors, sensors and actuators can also be controlled by radio. In addition, as an alternative to wired sensors, an external radio temperature sensor, radio motion detector, a radio temperature sensor for changeover function and radio window contacts/handles can be learnt in. The override by radio is possible by means of higher-level controller profile and cable-bound via Modbus. Radio and wired sensors and actuators are processed identically and can be used in any combination. This guarantees individual and energy-efficient room air conditioning. The device (front of glass in white or black) has a monochrome display and touch-sensitive control buttons. It has a timer with three time channels of four time periods each. Mounting is designed for a flush-mounted box. For hotel applications, the device offers the option of an additional zone (bathroom heating) in conjunction with room temperature sensor and radio actuator SAB+/SAB05.

Measuring valuestemperature
Output voltagetypes AO2DO: 0..10 V = (to control 6-way control valve), types 3AO: 3x 0..10 V = (to control 6-way control valve, heating & cooling)
Output switch contacttypes AO2DO: 2x contact NO (1x heating, 1x cooling)
Network technologyRS485 Modbus
Radio technologyEnOcean (IEC 14543-3-10)
Frequency868 MHz
Power supply100..240 V ~, types 3AO: 15..24 V = (±10%) or 24 V ~ (±10%) SELV
Power consumptionmax. 2 VA
Measuring range temp.0..+50 °C
Accuracy temperature±1 K (typ. at 21 °C)
Inputs1x input for floating contact, 1x input for NTC10k or floating contact
Control functionssetpoint 0..+50 °C
Functionsintegrated PI and two-/three-position controller, MSG-Server for 2nd zone
DisplayLCD 60x44 mm, 240x160 px, backlight cold white
EnclosurePC, pure white, black, glass
ProtectionIP30 according to EN 60529
Connection electricalterminal block, max. 1,5 mm², inputs: terminal block, max. 1,0 mm²
Ambient condition0..+50 °C, max. 85% rH non-condensing
Mountingflush-mounting in standard EU box (Ø=60 mm, min. depth=45 mm)
Contact

Contact us:


Thermokon Sensortechnik GmbH
Platanenweg 1
35756 Mittenaar
Tel.: +49 2778 6960-0


Write email


View contact