STC-DO

The bidirectional flush-mounted radio receiver for EasySens® devices with relay output. The basic function can be configured individually by the user for heating with PWM, heating on/off, signal contact, hygrostat control, heating/cooling with PWM, light on/off or for fan release using the free Thermokon airConfig software as required.

Output switch contactchangeover contact, 24 V: floating, load max. 3 A, 240 V: non-floating, load max. 10 A
Radio technologyEnOcean (IEC 14543-3-10)
Frequency868 MHz, optional:, 902 MHz (Americas)
Antennainternal transmitting/receiving antenna
Data transmissionbidirectional, airConfig ready
Power supply24 V: 15..24 V = (±10%) or 24 V ~ (±10%) SELV, 240 V: 100..240 V ~
Power consumption24 V: typ. 1,5 W (24 V =) | 3,4 VA (24 V ~), 240 V: max. 0,5 VA (standby)
EnclosureABS, red
ProtectionIP20 according to EN 60529
Connection electricalterminal block, max. 1,5 mm²
Ambient condition-20..+60 °C, max. 85% rH non-condensing
Weight55 g
Mountingflush-mounting in standard EU box (Ø=60 mm, min. depth=45 mm)
Notesto use the free software airConfig (download) a USB stick, which is able to send and receive EnOcean telegrams, is necessary. The EnOcean USB stick (incl. license) is included in airScan (item No. 566704 for 868 MHz)
Contact

Contact us:


Thermokon Sensortechnik GmbH
Platanenweg 1
35756 Mittenaar
Tel.: +49 2778 6960-0


Write email