LP+

Room pendulum sensor for measuring CO2 in large rooms (open space offices, production halls, ...). For direct connection onto a DDC or a monitoring system, the LP+ provides an analogue 0..10 V output.

Measuring values CO2
Output voltage 0..10 V or 0..5 V (adjustable via jumper), min. load 10 kΩ
Power supply 15..35 V = or 19..29 V ~ SELV
Power consumption max. 2,5 W (24 V =) | 4,3 VA (24 V ~)
Measuring range CO2 0..2000 ppm
Accuracy CO2 ±50 ppm +3% of measured value (typ. at 21 °C, 50% rH)
Calibration self-calibration, Dual Channel
Sensor NDIR (non-dispersive, infrared)
Enclosure enclosure USE-L, PC, pure white, with removable cable entry
Protection IP65 according to EN 60529
Cable entry Flextherm M16 for wire Ø=3..7 mm, removable
Connection electrical removable plug-in terminal, max. 2,5 mm², sensor wire white 5 m, for other lengths please request
Ambient condition 0..+50 °C, max. 85% rH short term condensation
Delivery contents incl. mounting base enclosure USE-L pure white, incl. universal mounting set (cover screw, self-drilling screws, dowels, spax screws and screw cover)
Contact

Contact us:


Thermokon Sensortechnik GmbH
Platanenweg 1
35756 Mittenaar
Tel.: +49 2778 6960-0


Write email


View contact