LK-S CO2 LON

Duct air quality sensor for detection of CO2, temperature and humidity. Designed for duct mounted applications with connection to a LON FTT system for up to 3 values.

Measuring values CO2, temperature + humidity
Network technology LON FT (free topology)
Power supply 15..24 V = (±10%) or 24 V ~ (±10%) SELV
Power consumption max. 3 W (24 V =) | 6 VA (24 V ~)
Measuring range temp. 0..+50 °C
Measuring range humidity 0..100% rH non-condensing
Measuring range CO2 0..2000 ppm
Accuracy temperature ±0,5 K (typ. at 21 °C)
Accuracy humidity ±2% between 10..90% rH (typ. at 21 °C)
Accuracy CO2 ±75 ppm, >750 ppm: ±10% (typ. at 21 °C)
Calibration self-calibration, Dual Channel
Sensor NDIR (non-dispersive, infrared)
Enclosure PA6, pure white, with quick lock screws
Protection IP65 according to EN 60529
Cable entry M20 for wire max. Ø=8 mm, seal insert for double cable entry for wire max Ø=6 mm
Connection electrical terminal block, max. 1,5 mm²
Pipe PA6, black, Ø=19,5 mm, length 180 mm
Filter stainless steel wire mesh
Ambient condition 0..+50 °C, max. 85% rH short term condensation
Delivery contents MF20 flange included
Contact

Contact us:


Thermokon Sensortechnik GmbH
Platanenweg 1
35756 Mittenaar
Tel.: +49 2778 6960-0


Write email